Wiring remote switches into the Alpha DAS

Technical Support - Repairs - Software - Manuals - Tech Tips - Legacy
OTHER OPTIONS
-REQUEST AN RA NUMBER- -REQUEST TECHNICAL ASSISTANCE-
-ALPHA INSPECTION SERVICE-
service@alpaharadioproducts.com

In 1-of-9 mode, the remote relay 'hot' wires (+12 or +24vdc) are connected to terminals 1, 2, 3, 4, 5, 6, A, B, or C.

The common return wires can be connected to any of the 3 GROUND connections on J2 or J4. All corresponding terminals on J2 and J4 are common, this is done to accommodate wiring situations where there are several remote relay locations.

The coil returns (labeled RETURNS ABCDEF) are only for the 1-of-36 configuration. They provide "switched ground" so that only the appropriate set of remote relays will operate when a number relay is operated i.e. A1, only the number 1 relay in the A group will operate. The difference between ground and coil returns is that the coil returns are grounded only when the corresponding letter relays (A-F) are operated.

Configuration of the DAS for 1-of-9 or 1-of-36 operation is set by the position of internal DIP-switch S1-3 :
S1-3 ON = 1-of-9
S1-3 OFF = 1-of-36